Technical learning page. Best for engineers, designers and trade specialists who need the method, assumptions and evidence. It is not a substitute for site-specific design or current manufacturer data.
This connected example shows how continuity, Reynolds number, Colebrook-White, Darcy-Weisbach and the energy balance work together. Every input is invented for teaching. Nothing here describes an actual site, product or manufacturer value.
Inputs
- Flow: 180 L/min = 0.003 m³/s.
- Actual internal diameter: 50 mm = 0.05 m.
- Straight pipe length: 100 m.
- Equivalent roughness: 0.01 mm = 0.00001 m.
- Kinematic viscosity: 0.000001 m²/s.
- Density: 1000 kg/m³.
- Reference gravity: 9.80665 m/s².
- Inlet running pressure: 300,000 Pa.
- Elevation rise: 5 m.
Calculation sequence
- Internal area is 0.001963 m² and average velocity is 1.528 m/s.
- Reynolds number is 76,394 and relative roughness is 0.0002.
- The Colebrook equation gives a Darcy factor of 0.01992.
- Straight-pipe friction head loss is 4.743 m, corresponding to approximately 46.51 kPa under the stated assumptions.
- With equal end speeds, no pump and no other losses, pressure after the 5 m rise is approximately 204.46 kPa, or 2.045 bar.
What the result does not establish
Values are calculated at full precision and displayed rounded to avoid implying field accuracy that the inputs do not support. The example omits fittings, valves, filters, outlet behaviour, pump curves, water quality, transients, safety requirements and pressure-dependent demand. The inlet flow is imposed rather than solved from a supply characteristic. It cannot establish how many sprinklers will operate or whether the pipe and pressure are suitable.
Evidence
The inputs are illustrative and synthetic. Each calculated step uses the methods linked from this page.