Non-Potable Irrigation Water: Identification and Separation

Non-potable means the water is not intended or demonstrated to be safe for drinking. It does not mean harmless. Rainwater, borehole, surface, recycled and treated waters can present different chemical and microbiological risks.

Identification system

  • Mark pipework and fittings according to the current applicable standard and water source.
  • Label outlets, tanks, controls, valves and access points clearly as non-potable where relevant.
  • Show source, direction of flow and operational information where needed.
  • Place identification at junctions, valves, penetrations and regular accessible intervals.
  • Maintain an as-fitted schematic and valve schedule.

Water Regs UK's pipe-identification leaflet summarises BS 1710 markings and distinguishes public-supply and other-source water. Its alternative-water guidance states that alternative supplies must not be directly connected to mains drinking water and that the water undertaker must be involved where supplies combine.

Separation and use

Identification is not backflow protection. Where mains top-up is permitted, use the approved physical separation arrangement, normally an appropriate break tank and air gap agreed for the risk. Prevent hoses, bypasses and temporary connections from bridging the separation.

Assess exposure before selecting irrigation method. Aerosols, public access, edible crops, animals, maintenance contact and contaminated surfaces may change the required treatment and controls. “Recycled” or “treated” does not itself establish suitability.

Commissioning checks

  1. Trace every outlet from the source and prove no cross-connection.
  2. Inspect labels from normal access positions.
  3. Test backflow and alarm arrangements using the approved procedure.
  4. Record water-quality basis, permitted uses and prohibited uses.
  5. Brief users and maintenance staff.

Safety boundary: never use taste, smell or colour to judge potability. Never create a temporary direct mains connection.

Assumption and limitation: marking requirements and permitted uses depend on jurisdiction, premises and source. Confirm with the local water undertaker and competent designer.

Related: mains break tanks and pipework identification.