Total Dynamic Head for Irrigation Pumps

Technical guidance: Confirm final pump selection against manufacturer curves and site measurements.

Dual vertical irrigation pump set with control equipment
An installed pair of vertical irrigation pumps with controls.

A pump should be selected for a required flow and head together. Flow alone is not enough, and the maximum pressure printed on a pump label is not the same as the pressure available at the irrigation equipment.

What total dynamic head means

Total dynamic head, commonly shortened to TDH, is the head the pump must add at the design flow to overcome elevation, required outlet pressure and hydraulic losses. Head is expressed as a height of the pumped liquid, normally metres of water.

For a straightforward irrigation duty, a useful design form is:

TDH = elevation head + required pressure head + pipe friction head + fitting and equipment losses

The suction arrangement must also be represented correctly. In an open system, the relevant static lift is the vertical difference between the source water level and the delivery reference point. Do not add the same elevation twice.

Convert pressure to water head

Near normal irrigation temperatures, 1 bar is approximately 10.2 metres of water head. Therefore a sprinkler requiring 3 bar at its inlet needs about 30.6 metres of pressure head before pipe and equipment losses are added.

Worked example

An irrigation zone needs 40 L/min at 3 bar. The irrigated area is 8 metres above the source water level. Calculated pipe and fitting loss at 40 L/min is 7 metres, and the filter and control valve account for another 3 metres.

  • Required pressure head: 3 × 10.2 = 30.6 m
  • Elevation head: 8 m
  • Pipe and fitting loss: 7 m
  • Filter and valve loss: 3 m
  • Estimated TDH: 48.6 m at 40 L/min

The pump curve must therefore be checked near 40 L/min and 48.6 m head. A pump that can produce 48.6 m only at zero flow does not satisfy this duty.

Losses that are often missed

  • Suction pipe and foot valve losses.
  • Filters as they become dirty.
  • Check valves, solenoid valves and pressure regulators.
  • Long pipe runs and small internal diameters.
  • Elevation to the highest operating outlet.
  • Minimum pressure required at the most hydraulically remote outlet.

Design margin

Allowance for uncertainty should be justified, not added blindly. An oversized pump can create excessive pressure, inefficient throttling, cycling and control problems. Where demand changes, check the full expected operating range rather than one point.

Suction and cavitation

TDH does not by itself prove that a pump has adequate suction conditions. Check the manufacturer’s net positive suction head requirements, source level variation, water temperature, altitude, suction losses and priming arrangement. Poor suction design can prevent the pump reaching its published curve and can damage equipment.

Related Irri Hub pages

Sources and limitations

See the US Department of Energy pumping systems sourcebook, the USDA NRCS Pumping Plant standard and the selected pump manufacturer’s own data. This worked example is instructional and is not a pump selection for a real site.