Irrigation Fault Finding: Start Here

Find the cause of an irrigation fault before changing settings or replacing parts. Choose the symptom below, then follow the measurement guides where more detailed checks are needed.

Start here: describe the symptom, make the system safe, then separate the water path from the control path. Record the original state before changing a programme, regulator, valve, pump setting or wiring.

Choose the symptom

What you see First route
Low, weak or intermittent pressure Low or intermittent irrigation pressure
A zone will not start, stop or close reliably Valve will not open or close
A zone runs at the wrong time or without an expected request Controller programming and unexpected operation
The pump starts and stops too often Pump cycling and pressure vessels
The pump will not establish flow or loses prime Pump will not prime or loses prime
Dripline waters unevenly Dripline not watering evenly
Pump controls with two labelled rotary isolators and illuminated status indicators
JK Irrigation photograph: labelled pump isolators, selector control and status indicators.

Make the first observations safely

  1. Identify the affected zone, valve, controller station, pump and water source.
  2. Record whether the fault is permanent or intermittent and what changed beforehand.
  3. Note whether it occurs at start, during running, at shutdown or while the system should be idle.
  4. Check for flooding, damaged electrical equipment, exposed conductors, overheating, abnormal noise or uncontrolled pressure.
  5. Stop and obtain competent help if the system cannot be observed safely.

Do not repeatedly reset a protective device, run a pump dry, open a pressurised valve or work live. HSE guidance requires secure isolation of electrical, hydraulic and other energy sources before work.

Separate hydraulic and controller faults

Controlled check What the result suggests
The valve operates manually and flow is normal The water path can pass the required flow. Check the programme, station command, sensor state, common wire, station cable, connections and compatible solenoid.
The valve will not pass water manually Check the source, isolation, filter, valve flow control, pressure conditions, blockage and valve condition after safe isolation.
The controller is set to off and flow stops An unintended programme, manual command, remote command or control configuration may be involved.
The controller is set to off but flow continues Confirm that the correct controller and valve were identified. Then investigate manual bleed, solenoid seating, debris, diaphragm condition and low-head drainage.
The pump runs but pressure or flow is poor Begin with the source, prime, suction, pump duty, restrictions, valves, leaks and measured operating point.
The pump does not run, trips or shows a drive fault Use the safe pump electrical symptom route and obtain competent electrical testing.

Use these results to choose the next check; they do not identify a faulty component on their own. Some valves need minimum pressure differential, and some controllers, decoders, latching solenoids and pump interfaces use different test methods. The installed instructions take priority.

Low or intermittent pressure

First decide whether every zone, one zone or only the furthest outlets are affected. Record static pressure, running pressure and flow at named test points. Repeat under the same valve positions and note other water use. If the source reading changes with the symptom, investigate the shared supply or pump. If the source stays stable but pressure falls across one component or route, work downstream methodically.

Valve fails to close or a zone runs unexpectedly

Cancel all controller commands and record the result. Check every programme and start time, manual watering, remote access, sensor or flow response and pump/master-valve assignment. If water continues with the command removed, distinguish continuing lateral drainage from sustained valve flow. Do not dismantle the valve until the water is isolated and pressure is relieved.

Pump cycles too frequently

Record pressure at each start and stop, cycle duration, whether water is being used and which zone is active. A small leak, passing valve, unsuitable control settings, loss of vessel charge, reduced drawdown, sensor instability or a mismatch between pump and demand can produce similar symptoms. Use the installed pump, control and vessel limits rather than a generic starts-per-hour rule.

Keep a fault record

Use the fault diagnosis evidence record. Include a marked-up plan, controller and equipment models, exact messages, photographs, pressure and flow readings with locations, timings, weather, recent maintenance and one controlled change at a time.

When to stop

Isolate and obtain competent help for electrical damage, repeated protective-device operation, uncontrolled pressure, flooding, contamination, unsafe excavation, a pump that is stalled or overheating, or any work beyond the operator's competence. Never bypass an RCD, overload, alarm, interlock, dry-run device or backflow protection.

Browse by brand Hunter · Rain Bird

Sources and limitations

This is a diagnostic route, not a substitute for the exact manufacturer instructions, site risk assessment, competent electrical work or a hydraulic design.