Irrigation Flow Sensors, Leak Detection and High-Flow Shutdown

A flow sensor measures; the controller decides what to do. Effective leak protection needs a compatible sensor, correct installation, a reliable normal-flow baseline and tested shutdown logic.

Rain Bird FG100 flow sensor
A Rain Bird FG100 inline irrigation flow sensor.

Design questions

  • What is the minimum and maximum expected flow across all zones in L/min?
  • Does the sensor's measuring range cover both values with useful accuracy?
  • Are pipe size, thread type, flow direction, filtration and straight-run requirements satisfied?
  • Is the pulse or signal type compatible with the controller, decoder or monitoring input?
  • Will a master valve close, a pump stop, or only an alarm be raised?

Build a baseline

  1. Commission one station at a time after flushing and repairing known leaks.
  2. Record stable flow and pressure for each station, including legitimate variation such as adjustable arcs or seasonal equipment.
  3. Set low- and high-flow boundaries using the controller manufacturer's method. Do not copy a percentage from another site.
  4. Test a controlled abnormal-flow condition and confirm the intended station isolation, master-valve closure or pump stop.

Worked check

If a healthy zone is measured three times at 58, 60 and 61 L/min, its observed commissioning range is 58 to 61 L/min. A shutdown threshold must sit above legitimate variation yet below damaging abnormal flow. The arithmetic alone cannot choose it: repeat tests, instrument accuracy, simultaneous devices and the controller's learning method must be considered and documented.

Rain Bird's FG100 information describes learned flow and monitoring for low or excessive flow when paired with a compatible controller. Its installation details and ranges are product-specific.

Limitations

Low flow can indicate a closed valve, blockage, failed pump or empty source; high flow can indicate a broken lateral, missing head or valve that has failed open. A sensor cannot identify the cause by itself. Air, debris, electrical interference, reverse flow and unsuitable pipe geometry can corrupt readings.

Safety boundary: test without creating uncontrolled discharge, flooding, dry running or pressure surge. Flow shutdown complements, but does not replace, pressure relief, backflow protection, pump protection and physical isolation.

Related: commissioning checklist and master valves and interlocks.