Night-Flow and Isolation Leak Testing for Irrigation

A night-flow test looks for water passing through a defined boundary when every known demand should be off. Night-time is often convenient, but the method is an isolation test, not proof that any unexplained flow is an irrigation leak.

Blue inline water meter and connected pipework in an open ground chamber
An inline water meter in an open irrigation chamber.

Define the test boundary

  • Identify the meter, its units, display resolution and pulse factor.
  • List every legitimate demand downstream, including toilets, troughs, process water, automatic top-up, filter backwash and irrigation.
  • Disable automatic irrigation and prevent an unintended pump start.
  • Tell affected users and protect any critical water-dependent process.
  • Record valve positions rather than relying on memory.

Basic test

  1. Confirm all intended demand is off and the meter is readable.
  2. Record the start reading and exact time.
  3. Observe for a period long enough to exceed the meter resolution without leaving the system unsafe.
  4. Record the finish reading and any known automatic event.
  5. If movement is abnormal, repeat the test and use existing safe isolations to narrow the section.

Worked rate check

If the meter advances by 0.060 m³ in 30 minutes, that is 60 litres in 0.5 hours. The average unexplained rate is 60 ÷ 0.5 = 120 L/h, or 2 L/min. This calculation does not locate the loss and remains subject to meter resolution, timing and hidden legitimate use.

Interpretation

Continuous movement may indicate a mainline leak, passing valve, automatic top-up or other demand. Intermittent movement may reflect a programmed event or storage refill. No visible movement does not exclude a small leak below display resolution or a fault isolated by a closed valve.

Safety and limitations

Do not shut a valve that supplies drinking water, livestock, fire protection, cooling or another critical service without authority and a safe plan. Do not enter chambers, excavate or open pressurised equipment to trace a result. Confirm whether the meter is suitable and correctly installed before treating its reading as an accurate measurement.