A night-flow test looks for water passing through a defined boundary when every known demand should be off. Night-time is often convenient, but the method is an isolation test, not proof that any unexplained flow is an irrigation leak.
Define the test boundary
- Identify the meter, its units, display resolution and pulse factor.
- List every legitimate demand downstream, including toilets, troughs, process water, automatic top-up, filter backwash and irrigation.
- Disable automatic irrigation and prevent an unintended pump start.
- Tell affected users and protect any critical water-dependent process.
- Record valve positions rather than relying on memory.
Basic test
- Confirm all intended demand is off and the meter is readable.
- Record the start reading and exact time.
- Observe for a period long enough to exceed the meter resolution without leaving the system unsafe.
- Record the finish reading and any known automatic event.
- If movement is abnormal, repeat the test and use existing safe isolations to narrow the section.
Worked rate check
If the meter advances by 0.060 m³ in 30 minutes, that is 60 litres in 0.5 hours. The average unexplained rate is 60 ÷ 0.5 = 120 L/h, or 2 L/min. This calculation does not locate the loss and remains subject to meter resolution, timing and hidden legitimate use.
Interpretation
Continuous movement may indicate a mainline leak, passing valve, automatic top-up or other demand. Intermittent movement may reflect a programmed event or storage refill. No visible movement does not exclude a small leak below display resolution or a fault isolated by a closed valve.
Safety and limitations
Do not shut a valve that supplies drinking water, livestock, fire protection, cooling or another critical service without authority and a safe plan. Do not enter chambers, excavate or open pressurised equipment to trace a result. Confirm whether the meter is suitable and correctly installed before treating its reading as an accurate measurement.
Related guides
- Flow sensors, leak detection and high-flow shutdown
- System losing pressure
- Meter readings and water-use baseline
- Water-efficiency audit